Electric Heat Operation; Bard Guard Anti-Theft System Option; Smoke Detector Option - Bard FUSION-TEC HR58APA Installation Support Materials

Hide thumbs Also See for FUSION-TEC HR58APA:
Table of Contents

Advertisement

Electric Heat Operation

The heat strip will be activated on a call for heat.
This call can be generated by the LV or the wall unit
operating in stand alone mode.

Bard Guard Anti-Theft System Option

The unit has the option to be shipped from the factory
with a low pressure switch, panel sensors and a
speaker. These devices are used with the Bard Guard
BG1000 anti-theft controller to provide an anti-theft
measure. These sensors and switch form a loop that
when connected to the BG1000 controller will cause
the system to go into alarm if any of the front panels or
coil assemblies are removed without being disarmed.
The speaker provides an audible alert that the system
is being tampered with. The Bard Guard anti-theft
control sensor connection is wired to terminals 7 and
8 on the wall unit. The speaker connection is wired to
terminals 5 and 6 on the wall unit. See the BG1000
controller manual for directions on connecting the wall
units to the BG1000 controller.

Smoke Detector Option

The unit is equipped with an input that requires a dry
contact. This will disable unit operation and is intended
to be used with a smoke detector (not supplied). When
this input indicates a smoke event, the system will be
shut down. The alarm will automatically clear when the
alarm condition is no longer present.
Page
47 of 53

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fusion-tec hr58apb

Table of Contents