4. Press UP or DOWN keys to scroll to Alarm Setup
(A4); press ENTER key.
5. Press ENTER key to scroll to Close Delay (see
Figure 2.37).
6. Press UP or DOWN keys to change to the desired
value.
7. Press ENTER key to save the value.
FIGURE 2.37
Adjusting Damper Failed to Close Delay

Damper Failed to Open Alarm

When the controller commands the economizer damper
actuator to a position other than 0% and the damper
switch indicates the damper is not open, after a delay
of 20 seconds the controller will generate a damper
failed to open alarm. This alarm is just a notification
and will not disable any features on the controller.
To adjust the damper failed to open delay:
1. Press MENU key to go to the Main Menu screen.
2. Press UP or DOWN keys and ENTER key to enter
USER password 2000.
3. Press UP or DOWN keys to scroll to System Config;
press ENTER key.
4. Press UP or DOWN keys to scroll to Alarm Setup
(A4); press ENTER key.
5. Press ENTER key to scroll to Open Delay (see
Figure 2.37).
6. Press UP or DOWN keys to change to the desired
value.
7. Press ENTER key to save the value.

Outdoor Temperature Sensor Failure Alarm

When the sensor reads a value that is outside of the
acceptable -41 to 303.0° range, an alarm will be
generated indicating the sensor has failed. This alarm
condition will disable the economizer.
This alarm is fixed and cannot be adjusted.

Outdoor Humidity Sensor Failure Alarm

When the sensor reads a value that is outside of the
acceptable 0 to 100% RH range, an alarm will be
generated indicating the sensor has failed. This alarm
condition will disable the economizer when the mode is
set to temperature and humidity or enthalpy.
This alarm is fixed and cannot be adjusted.

Supply Temperature Sensor Failure Alarm

When the sensor reads a value that is outside of the
acceptable -41.0 to 303.0° range, an alarm will be
generated indicating the sensor has failed.
This alarm is fixed and cannot be adjusted.

Dust Sensor Failure Alarm

When the sensor reads a value that is outside of the
acceptable 0 to 100% RH range, an alarm will be
generated indicating the sensor has failed. This alarm
is just a notification and will not disable any other
features on the controller.
This alarm is fixed and cannot be adjusted.

Dust Limit Alarm

The controller has adjustable software setpoints
(default to 80%) to indicate dust levels are too high
and disable the economizer operation for 30 minutes.
This alarm is not communicated to the NOC. Once
the conditions are no longer present, the alarm will
automatically clear.
To adjust the dust sensor alarm setpoint:
1. Press MENU key to go to the Main Menu screen.
2. Press UP or DOWN keys and ENTER key to enter
USER password 2000.
3. Press UP or DOWN keys to scroll to System Config;
press ENTER key.
4. Press UP or DOWN keys to scroll to Alarm Setup
(A9); press ENTER key.
5. Press ENTER key to scroll to Setpoint (see Figure
2.38).
6. Press UP or DOWN keys to change to the desired
value.
7. Press ENTER key to save the value.
FIGURE 2.38
Adjusting Dust Sensor Alarm Setpoing
NOTE: When the temperature outside is measured
at or below 0°F, the dust sensor alarm will be
Page
45 of 53

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fusion-tec hr58apb

Table of Contents