Modular Fire Panel
CTN
LSN 0300 A
LSN 1500 A
ANI 0016 A
NZM 0002 A
RMH 0002 A
RML 0008 A
IOS 0232 A
IOS 0020 A
FPE-5000-UGM
IOP 0008 A
ENO 0000 B
3.8

Power Loss of All Components of the FPA-5000

Component designation
MPC-xxxx-B
PRS 0002 A
PRD 0004 A
BCM-0000-B
CZM 0004 A
LSN 0300 A
LSN 1500 A
NZM 0002 A
ANI 0016 A
RMH 0002 A
RML 0008 A
IOS 0232 A
IOS 0020 A
FPE-5000-UGM
IOP 0008 A
ENO 0000 B
UPS 2416 A
FMR-5000
Bosch Sicherheitssysteme GmbH
Functional module
LSN improved Module 300 mA
LSN improved Module 1500 mA
Annunciator Module
Notification Appliance Zone Module
RMH 0002 A Relay Module (for high voltage)
Relay Module (for low voltage)
RS232 Communication Module
20 mA Communication Module
Interface Module
Input/Output Module
Fire Service Interface Module
Power loss
4.92 W
0.18 W
0.33 W
0.96 W (controller + green LED lights up)
1.44 W (per AUX with 1.06 A load)
1.65 W (for a line with 100 mA load)
3.36 W (for 4 lines with 100 mA load each)
1.50 W (AUX with 490 mA load)
2.72 W (LSN)
8.00 W (AUX)
14.70 W (LSN with 750 mA load)
0.96 W
0.62 W (all LEDs on)
1.16 W
1.04 W (all relays activated)
0.36 W
0.36 W
0.17 W
0.24 W
1.44 W (1 relay activated)
7.80 W (4 relays activated + key deposit heating active)
28.00 W
5.40 W
Product Information
Installation/Configuration Notes | en
Max. number
32
11
32
8
32
32
4
4
4
32
8
F.01U.028.089 | 5.4 | 2009.08