Modular Fire Panel
1.15.3

CZM 0004 A 4 Zone Conventional Module

The CZM 0004 A Conventional Module is used to connect certain conventional peripheries and
provides connections for four monitored conventional lines.
NOTICE!
In line with EN 54-13, each conventional line must be terminated with EOL modules for the
operation of fire detection systems.
Labeling
AUX1 + / AUX1 -
OUT1 - / OUT1 +
IN1 - / IN1 +
AUX2 + / AUX2 -
OUT2 - / OUT2 +
IN2 - / IN2 +
AUX3 + / AUX3 -
OUT3 - / OUT3 +
IN3 - / IN3 +
AUX4 + / AUX4 -
OUT4 - / OUT4 +
IN4 - / IN4 +
Technical specifications
Operating and display elements 8 LEDs (4 x red, alarm / 4 x yellow, fault)
Input voltage
Maximum current consumption
- Standby mode (all four zones)
- In the event of an alarm (all four
zones)
Maximum output voltage
Maximum output current
Max. line resistance
Dimensions (H x W x D)
Weight without packaging
Bosch Sicherheitssysteme GmbH
Connector
24 V DC auxiliary power supply zone 1
Zone 1 output low / Zone 1 output high
Zone 1 input low / Zone 1 input high
24 V DC auxiliary power supply zone 2
Zone 2 output low / Zone 2 output high
Class A zone 2 input low / Class A zone 2 input high
24 V DC auxiliary power supply zone 3
Zone 3 output low / Zone 3 output high
Class A zone 3 input low / Class A zone 3 input high
24 V DC auxiliary power supply zone 4
Zone 4 output low / Zone 4 output high
Class A zone 4 input low / Class A zone 4 input high
4 buttons (LED test)
20 V DC to 30 V DC / 5 V DC ± 5%
65 mA
65 mA + 100 mA per zone (at 24 V DC)
20 V DC ±5%
100 mA ±10% per zone
2 x 25 Ohm per zone
Approx. 127 x 96 x 60 mm (5.0 x 3.8 x 2.4 inches)
Approx. 135 g (4.8 ounces)
Product Information
Product Description | en
39
F.01U.028.089 | 5.4 | 2009.08