Modular Fire Panel
Technical specifications
LCD display/touch screen
Operating and display elements
Connections
Permissible length of CAN cable for
system networking
Recommended cable type for CAN
connection
Input voltage
Max. line resistance of power supply 18 Ohm
Maximum current consumption
Permissible operating temperature
Permissible storage temperature
Housing material and color
Dimensions
Weight
1.15

Functional modules

Each functional module has been developed for a specific function within the system.
All modules feature:
The plug contacts in the panel rail provide the power supply to the modules and handle all
data traffic between the module and control panel.
The module is automatically identified as soon as it is plugged in. Contact with peripherals is
achieved with compact plug/screw terminals.
If a module is replaced, the plug/screw terminals are simply re-fitted, thus eliminating the
need for time-consuming rewiring.
The activation options are defined in the FSP-5000-RPS Programming Software.
This defines what a detection point should activate in a certain state.
The functional modules have the following technical specifications in common:
Permissible operating
temperature
Permissible storage temperature -20 °C to 60 °C (-4 °F to 140 °F)
Relative humidity
Housing material and color
Safety standards
Protection class
Deviating technical specifications are listed for each product.
Bosch Sicherheitssysteme GmbH
robust, totally enclosed housings
replacement during operation
pluggable connection terminals
Product Information
LCD display with 320 x 240 pixels, touch screen with
127.5 mm x 170 mm (5.0 in. x 6.7 in.) active area
22 keys, 1 key switch, 11 LEDs
DC1 (power supply), DC2 (redundant power supply,
CAN1, CAN2, Ethernet 100BaseTX, USB (max. 3 m
[10 ft] cable length), RS232 (max. 3 m [10 ft] cable
length), 2 signal inputs (IN1/IN2)
L
= 1000 m (3280 ft), depending on configuration,
max
cable type and topology
J-Y-ST/Y2x2x0.8
11 V DC to 30 V DC from FPA-5000 or FPP-5000
- Standby mode: 130 mA at 24 V DC
- In the event of an alarm: 225 mA at 24 V DC
-5 °C to 50 °C
-20 °C to 70 °C
ABS plastic, (UL94 V-0), light gray, similar to RAL 7035
(H x W x D) 280 x 340 x 87.2 mm (11.0 x 13.4 x
3.4 inches)
Approx. 3000 g (6.6 lb)
-5 °C to 50 °C (23 °F to 122 °F)
Max. 95% non-condensing
ABS plastic (UL94 V-0), satin finish, anthracite, RAL 7016
EN 60950
IP 30