30
40
Figure 3.4 Diagram for calculating the maximum achievable cable length, using elements with LSN
technology and the LSN 1500 A
L =
N =
a =
b =
NOTICE!
Remote alarm indications activated by the detector C point:
A maximum 500 m of additional cable length is allowed when using remote displays (e.g.
MPA/FAA-420-RI).
The total length of installed line must not exceed the limit of 3000 m!
3.5

Limits of SG 200 application

The cable resistance depends on the number of acoustic signaling devices.
Limits:
Maximum of 500 mA from the NZM 0002 A. Minimum voltage of 10 V at last SG 200 in loop.
Number of
SG 200
Bosch Sicherheitssysteme GmbH
a
5mA
4mA
3mA
50
60
70
80
90 100 110 120 130 140 150 160 170 180 190 200 210 220 230 240 250
Cable length in meters
Number of LSN elements
Bus dynamic limit
Maximum possible number of LSN
Maximum cable
resistance R
L
1
300
3
100
6
50
8
40
10
30
15
20
Product Information
2,5mA
2mA
elements = 254
improved
Maximum cable
[Ω]
length [m]
4100
1370
685
548
411
274
Installation/Configuration Notes | en
1,25mA
1,5mA
Maximum distance first
SG 200 - NZM 0002 A [m]
2050
685
342
274
205
137
F.01U.028.089 | 5.4 | 2009.08
61
0,265mA
0375mA
0,5mA
0,7mA
1mA