Pipe insulation
Insulating the pipe located inside of the outdoor unit
With a pipe insulator, insulate the pipe up to whole service valve located inside of the outdoor unit.
Seal the gap between the outdoor unit pipe and the insulator. Rainwater and dewdrops may soak through
the gap between the pipe and the insulation of the outdoor unit installed on the outside.
Separate the cover of the pipe and close it after insulation work. Only remove a knock-out hole cover
where the pipe will be installed. If the knock-out hole is open unnecessarily, it must be closed. If not, small
animals such as squirrels and rats may get into the unit through the hole and the unit may be damaged.
H/P
H/R

Charging refrigerant

The R410A refrigerant is blended refrigerant. Add only liquid refrigerant.
Measure the quantity of the refrigerant according to the length of the liquid side pipe. Add quantity of the
refrigerant using a scale.
Important information: regulation regarding the refrigerant used
it must be checked for leakage at least once every 12 months, according to regulation No. 517/2014.
WARNING
book, with all the information recorded, according to REGULATION (EU) No. 517/2014 OF THE