Connected - Samsung AMxxxJXV Series Installation Manual

Dvm s
Table of Contents

Advertisement

Caution
Refrigerant pipes must
be connected by the
side of the product.
Branch joint between
outdoor units must be
installed horizontally.
Install a vertical trap in
following cases as shown
Case1. Pipe length
between outdoor unit
branches exceeds 2m.
Case2. Pipe length
between outdoor unit and
its branch exceeds 2m.
Examples of refrigerant pipe installation
H/P
1. Using Y-joint
Correct installation
Straight section
should be 300mm
or more
1 m or less
Over 2 m
1 m or less
Over 2 m
Incorrect installation
Over 2 m
Over 2 m
55

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Amxxxkxv seriesAm120jxvagh/etAm100jxvagh/etAm080jxvagh/etAmxxxmxv seriesAm140kxvagh/et ... Show all

Table of Contents