Refrigerant pipe installation
Installing the branch joints
Branch joints must be installed 'horizontally' or 'vertically' .
Horizontal installation
Vertical installation
reducer.
NOTE
according to the diameter of the connection pipe, before connecting them.
Make sure that the pipe is not bent at where it is connected to the branch joint.
CAUTION
Keep a minimum straight line distance of 500mm or more before connecting branch joint.
Connect to
indoor unit
62
After branching
Socket
Pipe
Gas side/Liquid side branch joint
Before branching
Connect to other branch joint or indoor unit
Pipe connection
Socket
After branching
Minimum straight
line (over 500mm)