Space requirement for installation

System air conditioner may cause static noise when listening to AM stations. Therefore, select
an installation location for indoor unit where electrical wiring can be done while keeping certain
CAUTION
distance from a radio, computer and stereo equipment.
Especially, keep the unit at least 3m away from the electrical equipment in an area with weak
electromagnetic waves and put the main power cable and communication cables in a separately
installed protection tube.
Make sure that there is no equipment that generates electromagnetic waves. If not
electromagnetic waves may cause problem to the control systems which may lead to air
conditioner malfunction. (Example: Remote control sensor of the indoor unit may not receive
the signal very well, due to ballast stabilizer of the lighting equipment.)
In regions with heavy snowfall, make sure to install the outdoor unit where there is no concerns
of direct snowfall on the outdoor unit. Also, build higher base support so that accumulated snow
does not block the air inlet or the heat exchanger.
any concerns for exceeding dangerous level of refrigerant concentration in case of refrigerant
leakage, extra ventilation system is required.
When you install the outdoor unit in high places such as roof, install fence or guardrail around it.
When there is no fence or guardrail, service person could fall.
Do not install the product in places where corrosive gases such as sulfur oxides, ammonia, and
sulfurous gas are produced. (e.g. Toilet outlet, ventilation opening, sewage works, dyeing complex,
cattle shed, sulfuric hot spring, nuclear power plant, ship etc.) When installing the product in
those places, contact an installation specialty store as the copper pipe and brazing part will need
additional corrosion proof or anti-rust additive to prevent corrosion.
it on to the product.
Depending on the condition of power supply, unstable power or voltage any cause malfunction of
the parts or control system. (At the ship or places using power supply from electric generator...etc)
Make sure to install MCU when using HR products.
When you select the location to install MCU, the location is far away from indoor rooms because
the refrigerant running of MCU may create noise.
Space requirement was decided based on following conditions; Cooling mode, outdoor temperature of
easily by quantity of solar radiation.
When you secure installation space, consider path for people and the direction of the wind.
Secure installation space as shown in the below illustration, considering ventilation and the service space.
If the installation space is narrow, installer or other worker may get injured during work and may also cause
problem to the product.
If you install multiple number of outdoor units in one space, make sure to secure enough ventilation space
secured, product may malfunction.
You may install the outdoor units with 20mm of space between the product, but product's performance
may decrease depending on the installation environment.