Am240Kxvggh/Et - Samsung AMxxxJXV Series Installation Manual

Dvm s
Table of Contents

Advertisement

This device is intended for the connection to a power supply system with a maximum permissible
system impedance shown in the table (on the left page) at the interface point (power service box)
NOTE
of the user's supply.
requirement above. If necessary, the user can ask the public power supply company for the system
impedance at the interface point.
This equipment complies with IEC 61000-3-12 provided that the short-circuit power Ssc is greater
than or equal to Ssc(*2) at the interface point between the user's supply and the public system.
It is the responsibility of the installer or user of the equipment to ensure, by consultation with the
distribution network operator if necessary, that the equipment is connected only to a supply with a
short-circuit power Ssc greater than or equal to Ssc(*2).
[Ssc (*2)]
Model

AM240KXVGGH/ET

AM260KXVGGH/ET
AM240MXVGNR/ET
AM260MXVGNR/ET
AM140KXVAGH/ET
AM160KXVAGH/ET
AM180KXVAGH/ET
Ssc [MVA]
3.1
AM200KXVAGH/ET
4.5
AM220KXVAGH/ET
5.3
AM240KXVAGH/ET
5.3
AM260KXVAGH/ET
6.6
AM100MXVDGH/ET
7.6
AM120MXVDGH/ET
8.0
AM140MXVDGH/ET
8.6
AM160MXVDGH/ET
12.5
AM180MXVDGH/ET
12.2
3.1
4.5
5.3
5.3
6.6
7.6
8.0
8.6
12.5
12.2
3.1
4.5
5.3
5.4
7.2
8.8
Model
Ssc [MVA]
8.1
8.6
12.5
12.2
4.5
5.3
5.4
7.2
8.8
73

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Amxxxkxv seriesAm120jxvagh/etAm100jxvagh/etAm080jxvagh/etAmxxxmxv seriesAm140kxvagh/et ... Show all