Size of the pipe between branch joints (B)
Select the pipe size according to the sum of indoor unit capacity which will be connected after the branch.
However, if the size of the pipe between branch joints (B) is bigger than the size of the pipe connected to
the outdoor unit (A), apply the pipe size (A).
15.0 kW and below
Over 169.0 kW
Note1) If Ø 25.40 pipe is not available on site, use Ø 28.58 pipe.
Note2) If Ø 31.75 pipe is not available on site, use Ø 34.92 pipe.
Note3) If Ø 38.10 pipe is not available on site, use Ø 41.28 pipe
Size of the pipe between the branch joint and the indoor unit
Make a selection according to outdoor unit capacity.
Indoor unit capacity (kW)
Branch pipe length within 45m
Liquid pipe
Low pressure
(mm)
gas pipe(mm)
Ø 15.88
Ø 9.52
Ø 19.05
Ø 22.22
Ø 12.70
Ø 28.58
Ø 15.88
Ø 34.92
Ø 19.05
Ø 41.28
Ø 22.22
Ø 53.98
Branch pipe length between 45~90m
High pressure
Liquid
gas pipe(mm)
pipe(mm)
Ø 15.88
Ø 12.70
Ø 19.05
Ø 15.88
Ø 22.22
Ø 19.05
Ø 28.58
Ø 22.22
Ø 34.92
Ø 41.28
Ø 25.40
note1)
Liquid pipe
Ø 6.35
Ø 9.52
Ø 9.52
Ø 9.52
Low pressure
High pressure
gas pipe(mm)
gas pipe(mm)
Ø 19.05
Ø 15.88
Ø 22.22
Ø 25.40
note1)
Ø 19.05
Ø 28.58
Ø 22.22
Ø 31.75
note2)
Ø 28.58
Ø 38.10
note3)
Ø 41.28
Ø 34.92
Ø 53.98
Ø 41.28
Gas pipe
Ø 12.70
Ø 15.88
Ø 19.05
Ø 22.22
43