4.6

Test Run Checklist

Review the checklist before performing a test run. Check each item that applies.
No.
1
Thoroughly read the manual before performing a test run.
2
Turn the power on.
3
Set the voltage for the power supply to E1-01.
Check the items that correspond to the control mode being used.
No.
V/f Control (A1-02 = 0)
Select the best V/f pattern according to the application and motor characteristics.
4
Example: If using a motor with a rated frequency of 60.0 Hz, set E1-03 to "1".
5
Perform Auto-Tuning for Energy Savings if using Energy Saving functions.
Open Loop Vector Control (A1-02 = 2)
6
Uncouple the load from the motor when performing Rotational Auto-Tuning.
7
Perform Rotational Auto-Tuning.
The following data entered during Auto-Tuning should match the information
written on the motor nameplate:
motor rated output power (kW) → T1-02
rated voltage (V) → T1-03
8
rated current (A) → T1-04
base frequency (Hz) → T1-05
number of motor poles → T1-06
motor rotations per minutes (r/min) → T1-07
PM Open Loop Vector Control (A1-02 = 5)
9
Set permanent motor parameters E5-01 through E5-24
YASKAWA TM.V1000.01 V1000 Drive Installation & Start-Up Manual (Preliminary 01-19-07)
4.6 Test Run Checklist
Checklist
Checklist
Page
160
129
4
Page
143
162
164
165
168
122
181