Stopping

Normal Stop—A normal stop is initiated by rocking the
Start/Stop Switch on the controller front panel to the
Stop position and then releasing the switch. Holding
the switch in the Stop position energizes the AH
relay, causing further, unnecessary heating of the
air heater. In the Stop position, the Start/Stop switch
provides a ground through two blocking diodes to
energize the K4 relay (LED4 lights). The normally open
K4A contacts then close, latching the K4 relay in an
energized condition.
At the same time, normally closed K4B contacts open to
de-energize the FP (fuel pump) motor and the K25 relay.
The normally open K25 contacts then open to
de-energize the FS (fuel supply) solenoid, turning off the
flow of fuel. With the fuel supply and fuel pump both
turned off, the engine turns off.
With the engine turned off, the generator output decays
and causes relays K1 and K5 to de-energize (LED1 and
LED5 go out). The normally open K1D contacts then
open, de-energizing the K2 relay (LED2 goes out) and
opening the normally open K2 contacts to interrupt
power to the remaining controller relay circuits,
including relay K4. As a result, the latch-up of the K4
relay is broken to return the controller circuits to a normal
prestart condition.
TP-5606 6/02
12 VDC
AH
S
K25
10 A.
K20
10 A.
LED2
K3
K20
LED3
K2
K3
K4B
K25
K5
FROM SAFETY
SHUTDOWN
LED4
SWITCHES
K4
REMOTE PANEL
BV
K1F
HR
GEN
ON
K1A
VOLTAGE
REGULATOR
8 A.
MAIN FIELD
LED1
LED5
K1
K5
Figure 5-7. Three-Phase Generator Sequence of
Operation, Stopping
AIR HEATER
AH
M
FS
STOP/
B.C.
PREHEAT
ALT
START
S
K1C
K1D
K2
K1E
FP
K4A
K2
SDR
HR
OP
WT
K1B
OVERSPEED
PROTECTION
SDR
CIRCUIT BOARD
Controller Troubleshooting 5-7