WARNING
Sulfuric acid in batteries.
Can cause severe injury or death.
Wear
protective
clothing.
Battery acid may cause
blindness and burn skin.
Battery gases. Explosion can cause severe injury or
death. Battery gases can cause an explosion. Do not smoke
or permit flames or sparks to occur near a battery at any time,
particularly when it is charging. Do not dispose of a battery in a
fire.
To prevent burns and sparks that could cause an
explosion, avoid touching the battery terminals with tools or
other metal objects. Remove all jewelry before servicing the
equipment. Discharge static electricity from your body before
touching batteries by first touching a grounded metal surface
away from the battery. To avoid sparks, do not disturb the
battery charger connections while the battery is charging.
Always turn the battery charger off before disconnecting the
battery connections. Ventilate the compartments containing
batteries to prevent accumulation of explosive gases.
TP-5606 6/02
goggles
and
To further check generator set components, disconnect
the battery and remove wiring harness plugs from the
controller circuit board. Use an ohmmeter to check
continuity and to isolate defective components as
described in Figure 7-13. Also refer to the proper wiring
diagram in Section 9.
Before performing ohmmeter checks, disconnect
generator set battery to prevent damage to the
ohmmeter.
Component Testing and Adjustment 7-15