Kohler 15CCO Service Manual page 102

Commercial & recreational mobile generator sets
Table of Contents

Advertisement

D There must be continuity between leads 1 and 2.
D There must be continuity between leads 3 and 4.
D There must be continuity between leads 33 and 44.
D There must be continuity between leads 33 and 55.
D There must be continuity between leads B1 and
B2.
D There must be NO continuity between lead 1 and
leads 3, 4, 33, 44, and 55.
D There must be NO continuity between lead 1 and
leads B1 and B2.
D There must be NO continuity between lead 4 and
leads B1 and B2.
D There must be NO continuity between any stator
lead and ground on stator housing or frame
laminations.
D If any check fails, the stator must be repaired or
replaced.
7-20 Component Testing and Adjustment
Figure 7-16. Stator Resistance Check
33
44
Denotes
internal
connections only
1-847
Figure 7-17. Generator Stator Leads
1
2
3
4
55
B1
B2
TP-5414-7
TP-5606 6/02