Kohler 15CCO Service Manual page 29

Commercial & recreational mobile generator sets
Table of Contents

Advertisement

Remote Start and
Four-Meter Panel Kit
Allows starting/stopping from a location remote of the
generator set. The illuminated gauges include a DC
voltmeter,
engine
oil
temperature gauge, and generator running time
hourmeter which records total generator set operating
hours. Generator sets come equipped with a 6-pin
connector on controller back panel for connection of the
kit. Overall dimensions are 9 in. (229 mm) by 6 in. (152
mm) with a minimum depth of 4 in. (102 mm). Requires
Remote Connection/Extension Harness and sender kit.
See Figure 2-10 and Figure 2-11 for remote start and
four-meter panel features.
Figure 2-10. Remote Start and
Four-Meter Panel Features
Start-Stop/Preheat Switch--Rocker-type switch with
"ON" light used to start and stop the generator set.
During cold weather starts (below 50_F [10_C]):
Place controller start switch in STOP/PREHEAT
position for 15--20 seconds before attempting to start
generator set. This provides energizing of the glow
plugs.
DC
Voltmeter--Measures
battery(ies). Normal battery operating range is 12--14
Volts.
Engine Oil Pressure Gauge--Measures engine oil
pressure. Normal engine operating range is 36--50 psi
(248--345 kPa).
During the engine break-in period, it is normal for the
engine to produce higher oil pressure readings.
Water Temperature Gauge--Measures engine coolant
temperature. Normal engine operating range is
180--205° F (82--96° C).
TP-5606 6/02
pressure
gauge,
TT-873
voltage
of
starting
NOTE
Hourmeter--Records total generator set operating
hours for reference in maintenance scheduling.
+
water
P
10 A.
Fuse
P
P1-14
K2
K1
P2-3
53(70)
P3-2
(P3-4)
Violet
Yellow/
Red
Gen. 'ON'
Light
Water Temp.
Gauge
Oil Pressure
Gauge
DC Voltmeter
Hourmeter
single-phase systems may differ
from those for three-phase systems,
where they are different, the
single-phase numbers are shown
first followed by the three-phase
When the Start-Stop/Preheat
Switch is in the Start position,
Figure 2-11. Remote Start & Four-Meter Panel Kit
-
Stop/Preheat
Local
Switch
3(47)
2(43)
4(N)
Start
P2-4
P2-5
P2-6
Relay
Circuit
Board
P2-8
P2-9
P2-7
Grey/
Black
3(47)
2(43)
4(N)
P3-4
P3-1
(P3-5)
P3-5
Stop/
Black
(P3-6)
Preheat
Remote
Switch
Start
NOTE
Wire and pin numbers for
numbers in parentheses.
NOTE
contacts 3 and 4 are closed.
N
P1-9
W.T.
O.P.
Sender
Sender
P4-13
P4-10
(P4-2)
(P4-3)
10(5)
11(7C)
P3-3
P3-6
(P3-2)
(P3-3)
L.
Blue
Tan
TT-873
Operation 2-9