Installation
1.9

Timing and temperature control

The wall-mounted condensing gas boiler can be fitted with the
following control devices:
– ON/OFF temperature controller, volt free;
– A room-temperature control device at 230V connected to
the RTH converter see fig. 15, item 2.
1.9.1
230V Room-temperature control device
connection
CAUTION
DO NOT activate the condensing gas boiler at
this stage.
Lead the 230V control device wire through the cable lead
(see fig. 15, item 1).
Fix the 230V wire to position 1 and 2 of the 230V
connection (see fig. 15, item 2).
Secure the 230V wire with the bracket and the two screws
onto the RTH converter.
1.9.2
Volt free room-temperature control device
connection
Remove the cover of the connextion box (fig. 16, item 1).
Lead the control device wire through the cable lead
(see fig. 16, item 2).
Fix the wire to position 1 and 2 of the volt free connection
(see fig. 16, item 3).
Secure the wire with the bracket and the two screws onto
the RTH converter (see fig. 16, item 4).
Subject to modifications resulting from technical improvements!
Installation and maintenance instructions for wall-mounted condensing gas boiler Buderus 600 - 11R/19R/24R • 05/2004
Fig. 15 Connecting the control device
3
Fig. 16 RTH converter - Volt free connection
Boulter Buderus Ltd. • http://www.boulter-buderus.co.uk
1
1
2
1
2
19