Specifications - Johnson Controls VMA 1410 Overview And Engineering Manuallines

Variable air volume modular assembly
Hide thumbs Also See for VMA 1410:
Table of Contents

Advertisement

VMA1400 Series Overview and Engineering Guidelines Technical Bulletin

Specifications

Table 17: Specifications
Feature
Product Name
Product Code
Number
Single Unit
Bulk Pack
Buy American
Supply Voltage
Optional Fuse Current
Power Consumption
Ambient Operating
Conditions
Ambient Storage
Conditions
Terminations
Serial Interfaces
N2 Controller
Addressing
Communications Bus
Mounting
Housing
Dimensions
(L x W x H)
Actuator Torque
Shipping Weight
Electrical Inputs
Velocity Pressure
Outputs
Continued on next page . . .
Specification
Variable Air Volume Modular Assembly (VMA)
Cooling Only
Cooling with Reheat and/or
Models:
Fan Powered Models:
AP-VMA1410-0
AP-VMA1420-0
AP-VMA1410-0D
AP-VMA1420-0D
AP-VMA1410-0G
AP-VMA1420-0G
20-30 VAC at 50 or 60 Hz
0.6 ampere for VMA1410; 2.0 ampere for VMA1420; 1.2 ampere for VMA1430
VMA1410/1420: 10 VA maximum (relay and valve requirements not included)
VMA1430:
3 VA maximum (damper actuator, relay, and valve requirements
not included)
0 to 50°C (32 to 122°F)
-40 to 70°C (-40 to 158°F)
6.3-mm (1/4-in.) spade lugs (Communication has screw terminals.)
N2 Bus and Zone Bus
DIP switch set (1-253) Addresses 254 and 255 are reserved. Software addressable
with the HVAC PRO program Release 7.02 or later, or the VBT program
N2 between VMA and NCM/N30 (3-wire). Zone Bus between VMA and room sensor
(8-pin phone jack or wire to spade lugs or optional plug-on terminals)
One screw (included) mounts the VMA1410/1420 to the VAV box. One screw
attaches damper shaft to the actuator, 8-mm (5/16-in.) square head set screw with
44 N . m (375 lb . in) of axial holding power for up to 13-mm (1/2-in.) round damper
shafts. Minimum damper shaft length is 44.5 mm (1-3/4 in.). Use two screws
(included) to mount the VMA1430 to the VAV box.
Plastic housing for controller/actuator with UL 94-5VB Plenum Flammability Rating
VMA1410/1420: 153 x 102 x 102 mm (6 x 4 x 4 in.)
VMA1430:
153 x 102 x 83 mm (6 x 4 x 3.25 in.)
4 N . m (35 lb . in) minimum (VMA1410/1420 only)
VMA1410/1420: 13.1 kg (29 lb) for a box of ten, 1.3 kg (2.8 lb) each
VMA1430:
5 kg (10.6 lb) for a box of ten, 0.5 kg (1.06 lb) each
Analog Inputs:
• Nickel, silicon, or platinum (1 K ohm) or NTC (2.25 K) RTD room sensors,
1.6 K setpoint potentiometer (2-wire)
• Voltage input for 0-10 VDC (humidity or dew point sensor)
Binary Inputs:
Dry contacts
Input configurations vary based on model type.
Velocity Pressure for 374 Pascal (0-1.5 in. w.c.)
No outputs on VMA1410, except Stepper Motor
Binary outputs:
24 VAC triac switched, 25-500 mA loads
Stepper drive:
2 to 767 steps per second (23,000 step resolution)
(VMA1410/1420 only)
Analog output:
0-10 VDC @ 10 mA maximum
27
Models without
Actuators:
AP-VMA1430-0
AP-VMA1430-0D
AP-VMA1430-0G

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vma 1400 seriesVma 1430Vma 1420

Table of Contents