PECIFICATIONS
The terminal is expected to operate at moderate temperature variation, non-condensing
humidity variation, moderate vibration, and possible dust contamination.
Item
Input Power
Reader Interface
General Purpose Inputs
Relay Outputs
Red LED/Green LED
Outputs
Communications
Certifications
Mounting Specifications
Dimensions
Ambient Temperature
Humidity
Ventilation
M
AINTENANCE
This section provides maintenance instructions, operational testing procedures, and
information on replacement parts.
LEDs
The RDR2S-A module has 4 LEDs:
Power (Power): On during normal operation.
Status (STATUS): Blinks every second when unit is operational.
Transmit (XMIT): Blinks when a character is transmitted to the controller's
S300 bus.
Receive (RCV): Blinks when a character is received from the controller's
S300 bus.
24
Specification
+12 to +24VDC or 16 to 24VAC at24W
2-wire Wiegand (up to 256 bits)
12VDC, 250mA (typical), 500mA (peak)
Red indicator
Green indicator
Resistive load
1A max. 0-24VDC/VAC, 25VA max
50mA max. 0-24VDC.
These open collector outputs can be damaged with
!
the use of alternating current (AC) potentials as low
as 1VAC. The LED outputs can only be connected to
CAUTION
direct current (DC) loads up to 24VDC.
2 or 3-wire RS-485
FCC, Class B
CE Mark
C-Tick
DIN rail
Flat surface
5.7 H x 5.9 W x 2.2 D inches (14.4 cm x 15.0 cm x 5.5 cm)
32º to 122ºF (0º to 50ºC)
10 to 90% non-condensing
Cabinets require free movement of air over all exposed surfaces