Johnson Controls VMA 1410 Overview And Engineering Manuallines page 19

Variable air volume modular assembly
Hide thumbs Also See for VMA 1410:
Table of Contents

Advertisement

VMA1400 Series Overview and Engineering Guidelines Technical Bulletin
Single Duct Application Example 2
Table 8 illustrates the selections made through HVAC PRO software
for this example.
Table 8: Example 2 Questions
HVAC PRO Software Questions
Control Strategy
Supply Damper Actuator (DA1)
Fan Type (R)
Baseboard Heat Type (VA2)
Box Heat Type (VA1)
Warmup Initiation
Lighting Integration
Plenum
Supply
DPT1
TE2
C1
Figure 5: Single Duct Example 2 Mechanical Flow Diagram
Table 9: Single Duct Example 2 Bill of Materials
Component
C1, DPT1
DA1
TE1
TE2
VA1
VA2
R
* Box OEM manufacturers typically furnish fan relays and electric heat relays.
Configuration Selections
Pressure Independent, Single Duct
Floating/3-wire
Parallel Fan Temperature Controlled
Analog Output Valve
Floating/3-wire
Supply Air Temp Via a Hardware Input
No
R
DA1
TE1
Description
VMA
Damper Actuator
Zone Temperature Sensor
Supply Air Temperature Sensor
Valve Actuator Box Heat
Baseboard Heat Valve Actuator
Fan
H
Discharge
T
G
VA1
VA2
Sample3
Part Number
AS-VMA1430-0
Integrated with VAV box
TMZ1600
TE-6311P-1
VA-8020-1
VA-8052
*
19
B
A
S
E
B
D

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vma 1400 seriesVma 1430Vma 1420

Table of Contents