35. HOW TO SYNCHRONIZE CONFIGURATION

Function: After the configuration file of the master controller in FS18 automatic
fire alarm system is updated, the configuration file is issued through FC18-Bus
and the configuration file of each slave controller is updated accordingly.
Steps:
1.
Press "Menu" to browse the main menu (Fig. 35-1)
Main menu displayed.
2.
Press "→" to select "Brow" submenu (Fig. 35-2). Select "All" and then press
"OK". Now the tree diagram will be displayed in the window (Fig.35-3).
3.
Select the host machine in the tree diagram, then press "Menu" to browse
the main menu, and press "→" to select "Distribute cfgs" (Fig.35-3)
submenu to start the configuration distribution.
Note:
"Distribute cfgs" is available when there's misconfiguration in the
system.
Use the engineering tool FXS1800 to set the master controller. Only
the master controller can distribute and update the configuration file
of each slave controller.
The configuration distribution takes a long time when there are many
controllers in the system or the configuration file is large. The
distribution finishes when system is in below status:
There's no misconfiguration or distribute cfgs ongoing.
-
Each slave controller restarts and completes the initialization
-
Start "Distribute cfgs" after the system completes startup, which is
when the screen indicator stops flashing.
Operating Manual of FC18 Controller
Event
Brow Oper Conf Tool Help Login
Alarm & active
Alarm & active
Trouble
System Normal
Supervision
System Normal
SIEMENS Building
SIEMENS Building
Disable
SIEMENS
Test
Walk-Test
<2008-08-08 08:08:08>
Fig.35-1
Fig.35-2
Fig.35-3
Page: 54/70