The FC186x series controllers have three kinds:
-
FC1861 controller with 2 line card, max. 504 points
-
FC1862 controller with 4 line card, max. 1008 points
-
FC1863 controller with 6 line card, max. 1512 points

1. FEATURES

-
Fulfill Chinese Standard of GB4717-2005 and GB16806-2006.
-
Multi-language operation menu with windows style, easy and fast operation.
-
Shortcut key (right key) for popping out operation items of device/event.
-
Large memory space for up to 10000 history records, first in first out order, all events can be recorded during the
operation period.
-
LCD backlight Auto-off mode. When no operation or event to display within preset time, LCD backlight will be
automatically turn off. When there are events / operations, LCD will light up automatically to display events and/or
interlocking devices.
-
2 channels of programmable input/output (output: 40mA@24VDC, it can be programmed as general alarm output
or general trouble output; input: dry contact).
-
1 channel of NAC for audible and visible device (0.5A@24VDC).
-
8 channels of interlocking function (output: 40mA @ 24VDC ) for automatic control and manual operations of
control equipments.
-
Efficient group programming according to different using.
-
A FC186x controller can connect up to 2016 points by adding line card.
-
Network bus (FC18-BUS), the max. distance is 1000m (the twist wiring capacity is 1.0 to 1.5 mm
controllers can be networked.
-
FRT bus (FR18-BUS), the max. distance is 1000m (the twist wiring capacity is 1.0 to 1.5 mm
repeater displays can be networked.
-
Detection bus (FD18-BUS), 2-wire polarity-free, the max. distance for line resistance is 4000m, the max. distance
for line capacitance is 5000m. (the twist wiring capacity is 1.0 to 1.5 mm
-
Three user levels for different operation authority. Each user level is accessed by a pre-defined and changeable
password.
-
Convenient pluggable terminals with clear marks for field wiring.
-
Auto-mapping function to support on commissioning task.
-
Detection algorithm can be adjusted by controller according to environment, to provide high reliability of alarm and
reduce false alarm.
-
Programming can be done either directly on controller or through computer.
-
"Sticker Method" easy for commissioning on site.
Operating Manual of FC18 Controller

CHAPTER 1 SYSTEM OVERVIEW

2
). Up to 32 floor
2
)
2
). Up to 32