Fire Alarm Event Handling - Siemens FC18 Series Operating Manual

Hide thumbs Also See for FC18 Series:
Table of Contents

Advertisement

6.

FIRE ALARM EVENT HANDLING

Fire alarm status:
l
Fire alarm indicator turns on
l
Fire event with customer information shown in the LCD as the figure
l
Acknowledge/Silence indicator flashing
l
NAC activation indicator turns on
l
Buzzer turns on
l
NAC devices activated
How to handle:
1.
Press "Acknowledge/Silence" to silence the buzzer:
l
Under Level 1 interface, a login interface pops out automatically. Enter
Level 2/3 password and press "OK" to return back to alarm window
then press "Acknowledge/Silence". Now,
Buzzer is mute.
The "Acknowledge/Silence" indicator turns off.
NAC devices still in activation status.
l
Under Level 2/3 interface,
Buzzer is mute.
The "Acknowledge/Silence" indicator turns off.
NAC devices still in activation status.
2.
Press "NAC Activation" to deactivate NAC devices and the indicator turn off.
Press it again to reactivate NAC and the indicator turn on. So on and so
forth.
3.
Find out fire location from LCD.
4.
Go to the site to investigate the situation.
5.
Call the firemen immediately if it's an emergency. If it's controllable, after
handling the fire press "Reset" to remove the alarm event and the alarm
indicator turn off.
Handling multi-alarm:
Information of multi-fire alarm is displayed.
The highlight stays on the first alarm. Other alarms are displayed
repeatedly in a reverse order.
Browsing each alarm by pressing "↓" / "↑"
Note: There are 2 kinds of fire alarms namely "auto alarm" and "manual
alarm".
Operating Manual of FC18 Controller
Fig. 5-1fire alarm interface
Page: 24/70

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fc1862Fc1863Fc1861

Table of Contents