4.6

Servo amplifier setting initialization

Using the engineering tool (MR Mode Change packed with MR Configurator2) enables to initialize the setting of the servo
amplifier.
However, information related to the servo amplifier, including power-on cumulative time and the number of relays on/off, is not
initialized.
• The storage area of the servo amplifier has a life. Do not use this function frequently.
• Execute the initialization with the servo amplifier disconnected from the network and directly connected to
MR Mode Change via a USB cable.

Initialization procedure by MR Mode Change

Open MR Mode Change, and connect a servo amplifier and a personal computer with a USB cable. Switch on control circuit
power supply of the servo amplifier.
Servo amplifier
CN5
Confirm that "Reset to factory settings" is selected, and click "Write". After the writing is completed, cycle the power or reset
the software.
Cycling the power or resetting the software initializes the setting of the servo amplifier at start-up. Confirm that the initialization
has completed by reading the setting of the servo amplifier.
Personal computer
USB cable
To USB
MR-J3USBCBL3M
connector
(option)
4 STARTUP
4.6 Servo amplifier setting initialization
4
49