8.
Operation
Observe the instructions in section 3, "Safety instructions", in section 9, "Faults, causes and remedy", and
in section 10, "Maintenance and repair"!
The coating must not carry an electrostatic charge!
The operator must ensure that highly effective mechanisms which can set up a charge
in the coating are safely avoided.
During operation the gear unit must be monitored for:
Oil temperature
Correct oil level (see item 8.1 and section 7, "Startup")
Changes in gear noise
Possible oil leakage at the housing and shaft seals
Bearing vibrations with present measuring sequence.
If any safety device has triggered, it must only be possible to start the drive again after
releasing the reclosing interlock.
8.1
Oil level
To check the oil level, stop operation of the gear unit.
Depending on the type the following oil levels apply when the motor has cooled down:
When the oil is hot, the oillevel marks may be slightly exceeded. It must in no case be
allowed to fall below the mark. If necessary, top up to the correct level.
The oil level in the oilsupply system must be checked.
For this, the operating instructions of the oilsupply system must be observed!
8.2
Irregularities
The drive unit must be switched off at once,
if irregularites are found during the operation
or
if the pressuremonitoring device in the oilcooling system triggers alarm
(only with correspondingly equipped gear units).
Determine the cause of the fault, using table 18, "Faults, causes and remedy"
(see item 9.2).
Table 18, "Faults, causes and remedy", contains a list of possible faults, their causes
and suggested remedies.
If the cause cannot be found, a specialist from one of our customerservice centres
should be called in (see section 2).
Middle of the oilsight glass
Upper mark on the oil dipstick
BA 5033 EN 03/2011
The maximum permitted temperature is:
90 °C (applies to mineral oil)
At higher temperatures the gear unit must be shut
down immediately and Siemens customer service
consulted.
81 / 96