Default:
Explanation:
Name:
Range of val-
ues:
Default:
Explanation:
Name:
Range of val-
ues:
Default:
Explanation:
CP 1243-1
Operating Instructions, 04/2017, C79000-G8976-C365-03
0
Monitors the number of pulses sent by the master station (Count). If the
number of pulses received from the master station exceeds the value con-
figured here, the command is rejected.
If you enter 0 (zero), the monitoring is disabled.
Max. pulse duration
0 ... 65535
0
Monitors the pulse duration sent by the master (On-time). If the duration of
the pulse received from the master exceeds the value configured here, the
configurable "Pulse duration replacement time" is used.
If the "Pulse duration replacement time" is configured with zero, the com-
mand is rejected.
With 0 (zero) the "Pulse duration replacement time" is used for every pulse.
Pulse duration equivalent time
0 ... 65535
0
Replacement value for the pulse duration If the pulse duration received from
the master exceeds the value configured in "Max pulse duration". The pa-
rameter is only used when "Max. pulse duration" is configured.
If the value is 0 (zero), no replacement value is used.
If the ""Max. pulse duration" and "Pulse duration replacement time" are con-
figured with zero, the command is rejected.
Configuration
4.10 Data points
111