Snmp - Siemens CP 1243-1 Operating Instructions Manual

Communications processor for connecting the simatic s7-1200 to control center systems
Table of Contents

Advertisement

● Authentication ...
– Teleservice user name and password
Terminate online connection
On completion of the online session, terminate the online connection again using the
"Disconnect" button.
6.4

SNMP

SNMP (Simple Network Management Protocol)
SNMP is a protocol for management and diagnostics of networks and nodes in the network.
To transmit data, SNMP uses the connectionless UDP protocol.
The information on the properties of SNMP-compliant devices is entered in MIB files (MIB =
Management Information Base).
Range of performance of the CP as an SNMP agent
The CP supports data queries in the following SNMP versions:
● SNMPv1 (standard)
● SNMPv3 (Security)
It returns the contents of MIB objects of the standard MIB II according to RFC 1213 and the
Siemens Automation MIB.
● MIB II
The CP supports the following groups of MIB objects:
– System
– Interfaces
– IP
– ICMP
– TCP
– UDP
– SNMP
The following groups of the MIB II standard are not supported:
– Adress Translation (AT)
– EGP
– Transmission
CP 1243-1
Operating Instructions, 04/2017, C79000-G8976-C365-03
Here, enter the data for the TeleService user that you configured in STEP 7 in the
global Security settings, see also section Configuration of the TeleService access
(Page 80).
The "Interfaces" MIB object provides status information about the CP interfaces.
Diagnostics and upkeep
6.4 SNMP
125