Mitsubishi a2 Series Programming Manual page 121

Simple application controller
Table of Contents

Advertisement

α
2 Simple Application Controllers
The controller then records the way that the PV behaves and derives the correct parameter
using the Ziegler and Nichols formulas below. See Figures 6.22e and 6.22f for the definintions
of a, τ and τ
on.
Table 6.29: The Ziegler and Nichols formulas
Proportional gain K
Integration time T
Derivate time T
See figures 6.22e and 6.22f for the definitions of
Consequently, if the system is moderately linear, the Auto-tuned parameters will be sufficient to
control the PV if the SV is changed. Auto-tuning will not need to be performed again.
The following parameters should be adjusted before starting the Auto-tuning:
• Direction of operation (to ensure that MV drives PV in the correct direction)
• Set Value (Changes during Auto-tuning are not effective.)
• Sample Time (Must be larger than the maximum system scan time!)
• Noise filter
• Desired control characteristic after Auto-tuning (P-, PI- or PID-control)
• Output Upper and Lower limit values
• AT bias
The following parameters may also be set before Auto-tuning, but they do not influence the
process:
• Derivative gain
• Control Response type (fast, normal, slow)
Note concerning the VLS Programming Language: Upon the completion of
Auto-Tuning, the program in the controller will be updated with the new PID
parameters. If VLS was monitoring the controller before the Auto-Tuning function was
started, monitoring will STOP, a message box will appear and VLS will return to the
Editing mode. The updated program must be uploaded to the PC to begin monitoring
again.
P
PI
1
0.9
P
a
a
I
33
1 (
0
on
D
0
0
PID
1.2
a
on
on
)
20
1 (
)
on
on
50
1
on
a
, τ and τ
on.
Function Blocks 6
Unit
1
100 ms
10 ms
6 - 63

Advertisement

Table of Contents
loading

Table of Contents