Maintenance
9.1 Inspection and maintenance
Regreasing intervals
The necessary relubrication intervals depend essentially on the level of dirt in the environment
and on the ON time of the motor. For this reason, they can only be defined taking into account
the respective operating conditions. Make sure that the groove in the seal is full of grease at all
times.
9.1.11

Cleaning the cooling air ducts

The cooling ducts must be free of any pollution in order that the machine is adequately cooled.
● Regularly clean the grids, ducts, ribs, pipes etc. to remove dust and pollution.
9.1.12

Touch up any damaged paintwork

If the paint is damaged, it must be repaired in order to protect the unit against corrosion.
Note
Paint system
Contact the Service Center (Page 167) before you repair any paint damage. They will provide
you with more information about the correct paint system and methods of repairing paint
damage.
9.1.13

Repainting

Explosion hazard caused by incorrect painting
The paint coat can become electrostatically charged where there is a thick coat. Electrostatic
discharges can occur. There is a risk of explosion if potentially explosive mixtures are also
present at this moment. This can result in death, serious injury or material damage.
You must comply with one of the following requirements when you repaint painted surfaces:
● Limit the total paint film thickness according to the explosion protection group:
● Limit the surface resistance of the paint used:
128
WARNING
– IIA, IIB: Total paint coating thickness ≤ 2 mm
– IIC: Overall coating thickness ≤ 0.2 mm for motors of group II (gas)
– Surface resistance ≤ 1 GΩ for motors of groups II and III (gas and dust)
SIMOTICS FD 1MM1
Operating Instructions 02/2019