Appendix 2
Certification of UL, cUL standards
The FX5-ENET/IP supports UL (UL, cUL) standards.
For models that support UL standards, refer to the following.
UL, cUL file number: E95239
Compliance with EC directive (CE Marking)
This note does not guarantee that an entire machine produced in accordance with the contents of this note will comply with
the following standards.
Compliance to EMC directive and LVD directive of the entire mechanical module should be checked by the user/
manufacturer. For more details please contact to the local Mitsubishi Electric sales site.
Requirement for compliance with EMC directive
The following products have shown compliance through direct testing (of the identified standards below) and design analysis
(through the creation of a technical construction file) to the European Directive for Electromagnetic Compatibility (2014/30/
EU) when used as directed by the appropriate documentation.
Attention
This product is designed for use in industrial applications.
Product compatibility
Type: Programmable controller (open type equipment)
Models: FX5 manufactured
from October 1st, 2018
Electromagnetic compatibility (EMC) directive
EN61131-2:2007 Programmable controllers
- Equipment requirements and tests
Caution for compliance with EC Directive
Caution for when the FX5-ENET/IP is used
When the FX5-ENET/IP is used, attach a ferrite core and make 3 turns within approximately 200 mm from the power cable
connectors. (Ferrite core used in tests by Mitsubishi: ZCAT3035-1330 manufactured by TDK Co.)
APPX
134
Appendix 2 Standards
Standards
FX5-ENET/IP
Remarks
Compliance with all relevant aspects of the standard.
EMI
• Radiated emission
• Conducted emission
EMS
• Radiated electromagnetic field
• Fast transient burst
• Electrostatic discharge
• High-energy surge
• Voltage drops and interruptions
• Conducted RF
• Power frequency magnetic field