Appendix 3

This section describes the details of remote buffer memory addresses of the I/O module.
(1) Input response time setting (address: 0000H)
Set the input response time of the input module.
*1
0ms
*1
0.2ms
1.0ms
1.5ms
5ms
10ms
20ms
70ms
*1
For the extension input module connected to the main A/D converter module or the main D/A converter module, "0H:
0ms" and "1H: 0.2ms" cannot be set. If "0H: 0ms" or "1H 0.2ms" is set, an error occurs, the ERR. LED turns on, and the
operation stops. For details on each module, refer to the following: User's manual for the main module used.
(a) Enabling the setting
Turn on and off Operation condition setting request flag (RWw0.b9) to enable the setting.
(b) Default value
The default value is 10ms (5H).
(2) Output HOLD/CLEAR setting (address: 0001H)
Set whether to hold or clear the last status of each output for when the I/O module is disconnected from data link
or the CPU module is in STOP status.
CLEAR
HOLD
(a) Enabling the setting
Turn on and off Operation condition setting request flag (RWw0.b9) to enable the setting.
(b) Default value
The default value is CLEAR (0H).
Details of Remote Buffer Memory Addresses
Input response time
Output HOLD/CLEAR setting
Setting value
0H
1H
2H
3H
4H
5H
6H
7H
Setting value
0H
1H
APPENDICES
A
269