10.6

List of Error Codes

This section lists the error codes, error details and causes, and actions for the errors that occur in the processing for data
communications between the FX5-ENET/IP and external devices or that are caused by processing requests from the CPU
module on the own station.
The FX5-ENET/IP has the following error codes.
Type

EtherNet/IP communication error

Module error
Ethernet communication error
EtherNet/IP communication error
The EtherNet/IP communication error codes are stored in 'Class1 connection 1 to 32 error code' (Un\G6262 to Un\G6293).
The Class1 communication status 'Error status' (Un\G6034 to Un\6035) bit corresponding to the connection where the error
has occurred is turned on.
Error
Error name
code
102H
Access not possible
103H
Parameter error
104H to
Connection timeout
105H
106H
Target device invalid
107H
Memory error
10AH
Connection start error
10BH
Connection start error
10CH
Insufficient memory
10 TROUBLESHOOTING
122
10.6 List of Error Codes
Error code
102H to 2FFH
1080H to 3FA1H
C027H to C035H
Error details and causes
An error was detected in the memory.
A parameter error was detected.
A timeout occurred in the connection with the
external device.
The target device does not exist.
An error was detected in the memory.
Production processing failed to start.
Consumption processing failed to start.
There is insufficient memory available for
connection processing.
Reference
Page 122
Page 126
Page 129
Action
• Take measures to reduce noise.
• Reset the CPU module, and then switch it to RUN mode. If the error
occurs again even after the above action is taken, the possible
cause is a hardware failure of the module. Please consult your local
Mitsubishi representative.
• Use EtherNet/IP Configuration Tool for FX5-ENET/IP to write the
parameters to the module again.
• When performing UCMM communications, check whether the
setting details of the UCMM request area are correct.
• Check whether the operating status of the external device is normal.
• Check for errors in the line status.
• The line may be busy, so retry at a later time.
• The external device may not be able to send data at the specified
RPI due to a high communication load, so specify a larger RPI and
connect again.
• Use EtherNet/IP Configuration Tool for FX5-ENET/IP to write the
parameters to the module again.
• If the error occurs again even after the above action is taken, the
possible cause is a hardware failure of the module on which the
error occurred. Please consult your local Mitsubishi representative.
• Take measures to reduce noise.
• Reset the CPU module, and then switch it to RUN mode. If the error
occurs again even after the above action is taken, the possible
cause is a hardware failure of the module on which the error
occurred. Please consult your local Mitsubishi representative.
• Take measures to reduce noise.
• Reset the CPU module, and then switch it to RUN mode. If the error
occurs again even after the above action is taken, the possible
cause is a hardware failure of the module on which the error
occurred. Please consult your local Mitsubishi representative.
• Take measures to reduce noise.
• Reset the CPU module, and then switch it to RUN mode. If the error
occurs again even after the above action is taken, the possible
cause is a hardware failure of the module on which the error
occurred. Please consult your local Mitsubishi representative.
• Retry at a later time.
• Reset the CPU module, and then switch it to RUN mode. If the error
occurs again even after the above action is taken, the possible
cause is a hardware failure of the module on which the error
occurred. Please consult your local Mitsubishi representative.