Checking with the buffer memory

The status of the Class1 communication connections and the error details can be checked with the following buffer memory
areas.
• Class1 communication status 'Data link status' (Un\G6030 to Un\G6031)
• Class1 communication status 'Error status' (Un\G6034 to Un\G6035)
• Connection behavior error status 'Class1 connection 1 to 32 error code' (Un\G6262 to Un\G6293)
Status of each connection
'The connection status can be checked by checking the bit corresponding to each connection in 'Data link status' (Un\G6030
to Un\G6031), and 'Error status' (Un\G6034 to Un\G6035).
'Data link status' (Un\G6030 to Un\G6031) 'Error status' (Un\G6034 to Un\G6035)
Off
On
Off
On
No error is generated for combinations other than those listed above. For details on the Class1 communication status, refer to
the following.
Page 149 Class1 communication status
Error details of each connection
The error code of each connection can be checked with 'Class1 connection 1 to 32 error code' (Un\G6262 to Un\G6293).
For details on the buffer memory, refer to the following.
Page 149 Connection behavior error status
For error code descriptions, refer to the following.
Page 122 List of Error Codes

PING test

A PING test is used to check that an EtherNet/IP device exists on the same EtherNet/IP network.
The FX5-ENET/IP sends a packet to the EtherNet/IP device to check its existence (an echo request). Then, the FX5-ENET/IP
checks whether communication is possible by seeing whether a response (an echo response) is returned.
(1) Echo request
(2) Echo response
Check method
The following methods are available for checking the PING test.
■Checking from EtherNet/IP Configuration Tool for FX5-ENET/IP
Use EtherNet/IP Configuration Tool for FX5-ENET/IP to execute a PING test.
For details, refer to the following.
Page 72 [Ping] tab
Page 82 [General] tab
10 TROUBLESHOOTING
118
10.3 Checking the Network Status
Off
Off
On
On
(1)
(2)
Status of each connection
Not connected or data link not in operation.
Data link in operation. No error has occurred.
Error has occurred with data link not in operation.
Error has occurred with data link in operation.