Advertisement

5. Diagnosis

5.1. Diagnostics data on I/O mapping

The SI Unit can be allocated diagnostics data as digital input data on I/O mapping, if one of the
module, Diagnostics type 1 or Diagnostics type 2, is configured. Use PROFINET IO Controller's
software to select a requested diagnostics type to allocate the diagnostics data on I/O mapping.
5.1.1. Diagnostics type 1
General diagnostics 1
Bit
Description
0
System fault
1
Valve-coil(s) short circuit
2
Module error
3
Changed module layout
4
US1 Diagnostics
5
Reserved
6
Reserved
7
Reserved
Table. 5-1 Overview of Diagnostics type 1
Byte
Description
0
General diagnostics 1
1
General diagnostics 2
2
Valve diagnostics 1
3
Valve diagnostics 2
Table. 5-2 General diagnostics 1
0: No error on Diagnostics data on I/O mapping
1: At least one error on Diagnostics data on I/O mapping has occurred
0: No valve coil(s) have a short circuit
1: At least one valve coil has a short circuit
0: No module has an error
1: At least one connected module has an error
0: Module has not disconnected.
1: At least one module has disconnected.
0: US1 present
1: US1 has dropped (< approx. 19.2V DC)
Fixed 0
Fixed 0
Fixed 0
- 27 -
Explanation
No.EX※※-OMW0011-A