Parameter
Function
Name
STF terminal
178
function selection
STR terminal
179
function selection
RL terminal
180
function selection
RM terminal
181
function selection
RH terminal
182
function selection
RUN terminal
190
function selection
A,B,C terminal
192
function selection
SO terminal
197
function selection
Incre-
Initial
Range
ments
Value
0: Low-speed operation command (RL)
1: Middle-speed operation command (RM)
1
60
2: High-speed operation command (RH)
3: Second function selection (RT)
4: Terminal 4 input selection (AU)
5: JOG operation selection (JOG)
7: External thermal relay input (OH)
1
61
8: Fifteen speed selection (REX)
10: Inverter operation enable signal (X10)
0 to 5, 7, 8,
10, 12, 14,
12: PU operation external interlock (X12)
16, 18, 24,
14: PID control valid terminal (X14)
1
0
25, 60∗1,
16: PU-external operation switchover (X16)
61∗2, 62,
18: V/F switchover (X18)
65 to 67,
24: Output stop (MRS)
9999
25: Start self-holding selection (STOP)
60: Forward rotation (STF) ∗1
1
1
61: Reverse rotation (STR) ∗2
62: Inverter reset (RES)
65: PU-NET operation switchover (X65)
66: External-NET operation switchover (X66)
67: Command source switchover (X67)
1
2
9999: No function
∗1
∗2
0, 100: Inverter running (RUN)
1, 101: Up to frequency (SU)
3, 103: Overload alarm (OL)
4, 140: Output frequency detection (FU)
7, 107: Regenerative brake pre-alarm (RBP)
8, 108: Electronic thermal relay function
1
0
11, 111: Inverter operation ready (RY)
12, 112: Output current detection (Y12)
0, 1, 3, 4,
13, 113: Zero current detection (Y13)
7, 8,
14, 114: PID lower limit (FDN)
11 to 16,
15, 115: PID upper limit (FUP)
25, 26, 46,
47, 64, 70,
16, 116: PID forward/reverse rotation
80, 81, 90,
91, 93∗1,
25, 125: Fan fault output (FAN)
95, 96, 98,
26, 126: Heatsink overheat pre-alarm (FIN)
99,
46, 164: During deceleration due to power
100, 101,
1
99
103, 104,
107, 108,
47, 147: During PID control activated (PID)
111 to 116,
64, 164: During retry (Y64)
125, 126,
70, 170: PID output interruption (SLEEP)
146, 147,
164, 170,
80, 180: Safety monitor output (SAFE)
180, 181,
81, 181: Safety monitor output 2 (SAFE2)
190, 191,
90, 190: Life alarm (Y90)
193∗1,
91, 191: Fault output 3 (power-off signal) (Y91)
195, 196,
93, 193: Current average value monitor
198, 199,
9999∗2
95, 195: Maintenance timer signal (Y95)
96, 196: Remote output (REM)
1
80
98, 198: Alarm output (LF)
99, 199: Fault output (ALM)
9999, —: No function∗2
0 to 99: Positive logic
100 to 199: Negative logic
∗1
∗2
Parameter list
Description
(FR-HC/FR-CV connection)
Assigned to STF terminal (Pr. 178) only
Assigned to STR terminal (Pr. 179) only
pre-alarm (THP)
output (RL)
failure stop function (retained
until release) (Y46)
signal (Y93)∗1
"93" and "193" cannot be set in Pr. 192.
"9999" cannot be set in Pr. 197.
×
×
×
×
×
×
×