Before operation

3.3
Before operation
3.3.1

Simple mode parameter list

For simple variable-speed operation of the inverter, the initial setting of the parameters may be used as they are. Set the
necessary parameters to meet the load and operational specifications. Parameter setting, change and check can be made
from the operation panel. (For details of parameters,
POINT
Only simple mode parameters are displayed by the initial setting of Pr. 160 Extended function display selection. Set Pr.
160 Extended function display selection as required. (Refer to page 37 for parameter change)
Pr. 160
9999
Parameters classified as simple mode can be displayed.
(initial value)
Both the parameters classified as simple mode and the parameters
0
classified as extended mode can be displayed.
Parameter
Name
Number
0
Torque boost
1
Maximum frequency
2
Minimum frequency
3
Base frequency
Multi-speed setting
4
(high speed)
Multi-speed setting
5
(middle speed)
Multi-speed setting (low
6
speed)
7
Acceleration time
8
Deceleration time
Electronic thermal O/L
9
relay
Operation mode
79
selection
Terminal 2 frequency
125
setting gain frequency
Terminal 4 frequency
126
setting gain frequency
Extended function
160
display selection
40
Refer to Chapter 4 of the Instruction Manual (Applied)).
Description
Initial
Unit
Value
6%/4%/3/
0.1%
0 to 30%
2%∗
0.01Hz
120Hz
0 to 120Hz
0.01Hz
0Hz
0 to 120Hz
0.01Hz
60Hz
0 to 400Hz
0.01Hz
60Hz
0 to 400Hz
0.01Hz
30Hz
0 to 400Hz
0.01Hz
10Hz
0 to 400Hz
0.1s
5s/10s/15s∗
0 to 3600s
0.1s
5s/10s/15s∗
0 to 3600s
Rated
0.01A
inverter
0 to 500A
current
0, 1, 2, 3, 4, 6,
1
0
7
0.01Hz
60Hz
0 to 400Hz
0.01Hz
60Hz
0 to 400Hz
1
9999
0, 9999
Range
Application
Set when you want to increase a
starting torque under V/F control,
or when the motor with a load will
not rotate, resulting in an alarm
[OL] and a trip [OC1].
Initial values differ according to the
inverter capacity. (0.75K or less/
1.5K to 3.7K/5.5K, 7.5K/11K, 15K)
Set when the maximum output
frequency need to be limited.
Set when the minimum output
frequency need to be limited.
Set when the rated motor
frequency is 50Hz.
Check the motor rating plate.
Set when changing the preset
speed in the parameter with a
terminal.
Acceleration/deceleration time can
be set.
Initial values differ according to the
inverter capacity. (3.7K or less/
5.5K, 7.5K/11K, 15K)
The inverter protects the motor
from overheat.
Set the rated motor current.
Select the start command location
and frequency setting location.
Frequency for the maximum value
of the potentiometer (5V initial
value) can be changed.
Frequency for the maximum
current input (20mA initial value)
can be changed.
Parameter which can be read from
the operation panel and parameter
unit can be restricted.
Reference
Page
44
45
43
64
46
41
47
68
71
74