6. Press UP or DOWN keys to change to the desired
value.
7. Press ENTER key to save the value.
FIGURE 52
Adjusting Damper Alarm Delay

Damper Failed to Close Alarm

When the controller commands the economizer damper
actuator to the 0% position and the damper switch
indicates the damper is not closed, after a delay of 300
seconds the controller will generate a damper failed
to close alarm. This alarm will disable all functions of
the unit and the status message will display "Off by
Alarm". If the condition is remedied, the alarm will
automatically reset and the unit will resume normal
operation.
Disabling the damper switch in I/O Config disables this
alarm.
To adjust the damper failed to close delay:
1. Press MENU key to go to the Main Menu screen.
2. Press UP or DOWN keys and ENTER key to enter
USER password 2000.
3. Press UP or DOWN keys to scroll to System Config;
press ENTER key.
4. Press UP or DOWN keys to scroll to Alarm Setup
A4.
5. Press ENTER key to scroll to Close Delay (see
Figure 52).
6. Press UP or DOWN keys to change to the desired
value.
7. Press ENTER key to save the value.
Outdoor Temperature and Humidity Combination
Sensor
The unit is equipped with a combination outdoor
temperature and humidity sensor to monitor
outdoor conditions for the economizer operation.
The temperature is measured with a 10k ohm NTC
thermistor. The humidity is measured with a humidity
sensor that outputs a 4-20mA signal to the controller.
Troubleshooting information for this sensor is included
in the Troubleshooting section of this manual.
Manual 2100-695
Page
32 of 54
The outdoor temperature can be verified by:
1. Press MENU key to go to the Main Menu screen.
2. Press UP or DOWN keys and ENTER key to enter
TECHNICIAN password 1313.
3. Press UP or DOWN keys to scroll to I/O Config;
press ENTER key.
4. Press UP or DOWN keys to scroll to Outdoor Air
Sensor C3.
5. Reference the Value to see the input of the sensor
(see Figure 54).
6. To apply an offset, press ENTER key to scroll to
Offset.
7. Press UP or DOWN keys to change to the desired
value.
8. Press ENTER key to save the value.
FIGURE 53
Outdoor Air Sensor
The outdoor humidity can be verified by:
1. Press MENU key to go to the Main Menu screen.
2. Press UP or DOWN keys and ENTER key to enter
TECHNICIAN password 1313.
3. Press UP or DOWN keys to scroll to I/O Config;
press ENTER key.
4. Press UP or DOWN keys to scroll to Outdoor Hum
Sensor C6.
5. Reference the Value to see the input of the sensor
(see Figure 54).
FIGURE 54
Outdoor Humidity Sensor

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fusion-tec wr58bpaFusion-tec wr36bpbFusion-tec wr58bpb

Table of Contents