Pressure Service Ports - Bard FUSION-TEC WR36BPA Service Instructions Manual

Wall-mount air conditioner
Hide thumbs Also See for FUSION-TEC WR36BPA:
Table of Contents

Advertisement

Pressure Service Ports

High and low pressure service ports are installed on all
wall-mount units so that the system operating pressures
can be observed. Pressures are shown in Table 11.
This unit employs high-flow Coremax valves instead of
the typical Schrader type valves.
Full Load Cooling
Return Air Temp
Model
(DB/WB)
75/62
WR36
80/67
85/72
75/62
WR58
80/67
85/72
Part Load Cooling
Return Air Temp
Model
(DB/WB)
75/62
WR36
80/67
85/72
75/62
WR58
80/67
85/72
Low side pressure ± 4 PSIG
High side pressure ± 10 PSIG
Tables are based upon rated CFM (airflow) across the evaporator coil. If there is any doubt as to correct operating charge
being in the system, the charge should be removed and system evacuated and recharged to serial plate charge weight.
NOTE:
Pressure table based on high speed condenser fan operation. If condensing pressures appear elevated check
condenser fan wiring. See "Condenser Fan Operation" on page 24.
TABLE 11
Cooling Pressures
Pressure
75
80
Low Side
130
131
High Side
290
312
Low Side
139
140
High Side
297
320
Low Side
144
145
High Side
307
331
Low Side
129
130
High Side
318
340
Low Side
138
139
High Side
326
349
Low Side
143
144
High Side
337
361
Pressure
75
80
Low Side
119
125
High Side
268
288
Low Side
127
134
High Side
275
295
Low Side
131
139
High Side
285
305
Low Side
135
136
High Side
283
304
Low Side
144
145
High Side
290
312
Low Side
149
150
High Side
300
323
WARNING! Do NOT use a Schrader valve core removal
tool with these valves. Use of such a tool could result
in eye injuries or refrigerant burns!
To change a Coremax valve without first removing the
refrigerant, a special tool is required which can be
obtained at www.fastestinc.com/en/SCCA07H. See the
replacement parts manual for replacement core part
numbers.
Air Temperature Entering Outdoor Coil °F
85
90
95
100 105 110 115 120 125
132
134
135
136
334
359
384
411
141
143
144
145
343
368
394
422
146
148
149
150
355
381
408
437
131
132
133
134
365
389
414
440
140
141
142
143
374
399
425
451
145
146
147
148
387
413
440
467
Air Temperature Entering Outdoor Coil °F
85
90
95
100 105 110 115 120 125
131
136
140
143
308
331
354
378
140
145
150
153
316
339
363
388
145
150
155
158
327
351
376
402
136
137
137
138
327
350
375
402
145
146
147
148
335
359
385
412
150
151
152
153
347
372
398
426
137
138
139
140
439
468
498
530
147
148
149
150
450
480
511
544
152
153
154
155
466
497
529
563
136
137
137
139
467
495
527
553
145
146
147
149
479
508
537
567
150
151
152
154
496
526
556
587
146
148
149
150
405
432
460
490
156
158
159
160
415
443
472
503
161
164
165
166
430
459
489
521
138
140
141
142
428
456
486
416
148
150
151
152
439
468
498
529
154
155
156
157
454
484
515
548
Manual
2100-695
Page
41 of 54
142
564
152
578
157
598
140
584
150
599
155
620
149
522
159
535
165
554
143
547
153
561
158
581