Damper Blade; Damper Switch; Damper Failed To Open Alarm; Damper Failed To Close Alarm - Bard MEGA-TEC W090A Service Instructions Manual

Wall-mount air conditioner
Table of Contents

Advertisement

Damper Blade

The system utilizes three damper blades to bring
in outdoor air and exhaust space air for economizer
operation. Damper 1 is left intake, damper 2 is exhaust
and damper 3 is right intake. Damper blades are made
of sheet metal and are integrated into the equipment.
To view damper blade position:
1. Press MENU key to go to the Main Menu screen.
2. Press UP or DOWN keys and ENTER key to enter
TECHNICIAN password 1313.
3. Press UP or DOWN keys to scroll to I/O Config;
press ENTER key.
4. Press UP or DOWN keys to scroll to Analog
Outputs; press ENTER key.
5. Press UP or DOWN keys to scroll to Analog Outputs
1/4, Analog Outputs 2/4 or Analog Outputs 3/4
(see Figure 37).
FIGURE 37
Damper Blade Position
Manual 2100-671C
Page
28 of 59

Damper Switch

The economizer utilizes three magnetic switches (one
on each damper blade) to determine if the damper is
operating correctly. This switch will be closed when the
damper is closed and open when the damper is open.
To verify the status of the switch:
1. Press MENU key to go to the Main Menu screen.
2. Press UP or DOWN keys and ENTER key to enter
TECHNICIAN password 1313.
3. Press UP or DOWN keys to scroll to I/O Config;
press ENTER key.
4. Press UP or DOWN keys to scroll to Digital Inputs;
press ENTER key.
5. Press UP or DOWN keys to scroll to Digital Ins 2/2.
6. Reference the values for Damper 1, Damper 2,
Damper 3 and Damper 4 (see Figure 38).
7. The input will display ON when the damper is
closed (reflecting closed circuit on damper switch)
and will display OFF when the damper is open
(reflecting open circuit on damper switch).
FIGURE 38
Damper Switch

Damper Failed to Open Alarm

When the controller commands the economizer damper
actuator to a position other than 0% and the damper
switch indicates the damper is not open, after a delay
of 20 seconds the controller will generate a damper
failed to open alarm. This alarm is just a notification
and will not disable any features on the controller.
The alarm must be cleared by a user reset.

Damper Failed to Close Alarm

When the controller commands the economizer damper
actuator to the 0% position and the damper switch
indicates the damper is not closed, after a delay of 300
seconds the controller will generate a damper failed to
close alarm. This alarm is just a notification and will
not disable any features on the controller.
The alarm must be cleared by a user reset.