Blower Status Switch; Output Volts; Controller Cfm; Heating - Bard FUSION-TEC WR36BPA Service Instructions Manual

Wall-mount air conditioner
Hide thumbs Also See for FUSION-TEC WR36BPA:
Table of Contents

Advertisement

6. Press UP or DOWN key to change OFF to ON.
7. Press ENTER key to scroll to OV Speed.
8. Press UP or DOWN keys to adjust the speed to the
desired output. See Table 4A or 4B.
NOTE: If unit is operating at the time the blower
override is being enabled, adjustments must be
made to OV Speed first before switching Blower
Override on.
TABLE 4A
WR36BP* Blower Speeds

Mode

Percentage
High Sensible
Full Load Cooling
High Sensible
Part Load Cooling
Standard Full
Load Cooling
Standard Part
Load Cooling
Economizer Standard
Economizer High S/T

Dehumidification

TABLE 4B
WR58BP* Blower Speeds
Mode
Percentage
High Sensible Full
Load Cooling
High Sensible Part
Load Cooling
Standard Full Load
Cooling
Standard Part Load
Cooling
Economizer Standard
Economizer High S/T

Heating

Mode
Manual 2100-695
Page
20 of 54
Speed
94.0
9.4 v
1500
54.0
5.4 v
1100
63.0
6.3 v
1200
43.0
4.3 v
90.0
9.0 v
1450
63.0
6.3 v
1200
63.0
6.3 v
1200
19.0
Speed
Controller

Output Volts

75.0
7.5 v
2180
50.0
5.0 v
1705
55.0
5.5 v
1830
35.0
3.5 v
1335
45.0
4.5 v
1600
75.0
7.5 v
1950
35.0
3.5 v
1335
35.0
3.5 v
1335
WR58BP*
950
470
* Unit is rated for free blow non-ducted
operation with SGR-5W Supply Grille
and RGR-5W Return Grille.

Blower Status Switch

The unit is equipped with a differential pressure airflow
CFM
switch to monitor the blower (see Figure 31). If the
blower is turned on and the switch doesn't close to
indicate there is differential pressure between the inlet
and outlet of the blower, an alarm will be generated.
For switch settings, see Figure 32.
Differential airflow status can be viewed by:
3. Press UP or DOWN keys to scroll to I/O Config;
5. Reference 7 NoAir row and Val column (see Figure
33).
Rated Airflow
Nominal Rated CFM
Nominal Rated ESP
High
Low
950
1800
1400
TABLE 6
Indoor Blower Performance
Speed
High
ESP
Dry
Wet
(Inch H
0)
Coil
Coil
2
0.00
0.10
1885
1800
TABLE 7
Maximum ESP of Operation
Electric Heat Only
Model
Static Pressure*
-A0Z
.00"
-A05
.00"
-B0Z
.00"
-B06
.00"
0.00
0.10
Low
Dry
Wet
Coil
Coil
995
950
1470
1400