Blower Status Switch

The unit is equipped with a differential pressure airflow
switch to monitor the blower (see Figure 28). If the
blower is turned on and the switch doesn't open to
indicate there is differential pressure between the inlet
and outlet of the blower, an alarm will be generated.
For switch settings, see Figure 28.
Manual 2100-749
Page
20 of 68
Nominal Rated ESP
Low
3280
0.35
Dry
Wet
0)
Coil
Coil
2
8190
N/A
Static Pressure ("WC)*
1.00"
1.00"
1.00"
1.00"
1.00"
1.00"
1.00"
1.00"
1.00"
1.00"
1.00"
1.00"
1.00"
1.00"
1.00"
1.00"
FIGURE 28
Dirty Filter Switch and Blower Status Switch
Left and Right Dirty
Filter Switches
(W180 Set @ 1.40)
Differential airflow status can be viewed by:
1. Press MENU key to go to the Main Menu screen.
2. Press UP or DOWN keys and ENTER key to enter
TECHNICIAN password 1313.
3. Press UP or DOWN keys to scroll to I/O Config;
press ENTER key.
4. Press UP or DOWN keys to scroll to Digital Inputs
C1-1; press ENTER key.
5. Reference AIrflw 1 row and Val column (see Figure
29).
FIGURE 29
Verifying Differential Airflow Status
Left and Right Blower
Status Switches
(W180 Set @ 0.40)