Communication via RS485

5.6 Communication via P1 - only CU230P-2 HVAC, CU230P-2 BT

5.6
Communication via P1 - only CU230P-2 HVAC, CU230P-2 BT
P1 is an asynchronous master-slave communication between what is known as a Field
Cabinet (master) and the FLN devices (slaves). FLN stands for "Floor level network".
The master individually addresses the various slaves. A slave responds only if the master
addresses it. Communication between the slaves is not possible.
A Field Cabinet can have several FLN ports. You can connect up to 32 FLN devices to each
FLN port (slaves).
Settings in the controller
In the Field Cabinet, for each slave you must install what is known as a "Logical controller
(LCTR) point". In addition, in the Field Cabinet you must define the "Point numbers" for
communication.
An overview of the "Point Numbers" is provided on the following pages.
162
Function Manual, 04/2018, FW V4.7 SP10, A5E34229197B AE
Fieldbuses