Siemens Simatic PCS 7 Function Manual page 86

High availability process control systems
Hide thumbs Also See for Simatic PCS 7:
Table of Contents

Advertisement

High availability solutions in PCS 7
4.3 Solutions for communication
Figure 4-6
Transmission rate
You have two interfacing options for the gateway between PROFIBUS DP and PROFIBUS
PA. These result in different transmission rates on PROFIBUS DP.
● If you connect the DP/PA couplers via a PA-Link , a transmission rate of up to 12 Mbps is
possible on the PROFIBUS DP.
● If you connect the DP/PA couplers directly, the transmission rate on PROFIBUS DP is 45.45
Kbps.
● The transmission speed on the PROFIBUS PA is 31.25 Kbps.
Availability - redundant interfacing
In a redundant system, we recommend that you implement the connection to the PROFIBUS
DP redundantly (redundant IM 153-2).
If a PA bus cable, an IM 153-2 or a DP/PA coupler fails, the communication connection to the
field devices is retained. The AFD or AFS automatically switches the connection to the
available signal path.
86
Connection to a single PROFIBUS DP
High Availability Process Control Systems (V9.0)
Function Manual, 05/2017, A5E39221836-AA