Siemens Simatic PCS 7 Function Manual page 73

High availability process control systems
Hide thumbs Also See for Simatic PCS 7:
Table of Contents

Advertisement

You may connect one redundant AS per CPU without redundant communication modules.
Connection possibilities:
● Single connection of an AS 41xH with one CP each per CPU. Availability is then reduced
accordingly.
● Single connection of an AS 41xH via an internal Ethernet interface of the CPU. Availability
is then reduced accordingly.
● Redundant connection of an AS 410H via internal Ethernet interfaces of the CPU
AS 410 on redundant, high availability plant bus
An AS 410 can be connected to the redundant, high availability plant bus without
communication modules. You can find additional information on this in section "AS 410H on
redundant, high availability plant bus (Page 74)".
Availability - redundant, high availability plant bus
The block diagram for a redundant, high availability plant bus with two CPs each in both OS
servers and additional switches appears as follows:
In this system, one CP 16x3 can fail in each OS server or one CP 443‑1 in each subsystem
of the AS without this affecting the complete system. The plant bus (bus) is configured
redundantly and with redundant switches in each case. As a result, a failure of the bus
component and all components involved (switches) is covered.
Additional information
● Section "Connecting PC stations to the plant bus (Page 68)"
● Section "Media Redundancy Protocol (Page 59)"
● Section "How to configure a high availability plant bus (Page 117)"
● Documentation
● Manual
● Operating instructions
● Manual
High Availability Process Control Systems (V9.0)
Function Manual, 05/2017, A5E39221836-AA
PCS 7 Released Modules
SIMATIC Net Twisted Pair and Fiber-Optic Networks
SIMATIC NET; Industrial Ethernet Switches SCALANCE X-400
SIMATIC Communication with SIMATIC
High availability solutions in PCS 7
4.3 Solutions for communication
73