Note
In case of using the I/O modules redundancy, the diagnostic feature or capability needs to be
activated.
Redundant operation of I/O modules of ET 200SP HA
The following requirements must be met to operate redundant I/O modules of ET 200SP HA:
● PCS 7 as of V9.0
● CPU 410-5H as of firmware version V8.2
● Suitable I/O modules (documentation:
Redundant operation of S7-300 I/O modules of ET200M (PROFIBUS DP)
The following requirements must be met to operate redundant S7-300 I/O modules of ET200M
(PROFIBUS DP):
● PCS 7 as of V6.0
● H-CPU as of firmware version V3.1
● Suitable S7-300 I/O modules (documentation:
Required software and configuration
You select and configure the redundant modules in HW Config.
● In order for both subsystems of the H system to be able to address redundant input/output
modules, S7 driver blocks from the "Redundant I/O" library and PCS 7 driver blocks from
the
● Modules with the same article number and version number are configured redundantly to
one another
You interconnect the signals in the CFC chart. You can find information on this in the section
"Configuration of redundant signals (Page 151)".
When the user program is compiled, the required driver blocks are placed, interconnected and
configured automatically.
High Availability Process Control Systems (V9.0)
Function Manual, 05/2017, A5E39221836-AA
PCS 7 Library as of PCS 7 V9.0 are required in addition to the necessary hardware.
High availability solutions in PCS 7
PCS 7 - Released Modules )
PCS 7 - Released Modules )