ABB Relion REC670 Applications Manual page 90

Bay control version 2.1 iec
Hide thumbs Also See for Relion REC670:
Table of Contents

Advertisement

Section 5
Local HMI
IEC13000280-1-en.vsd
GUID-AACFC753-BFB9-47FE-9512-3C4180731A1B V1 EN-US
Figure 30: RJ-45 communication port and green indicator LED
1 RJ-45 connector
2 Green indicator LED
The default IP address for the IED front port is 10.1.150.3 and the corresponding subnetwork
mask is 255.255.255.0. It can be set through the local HMI path Main menu/Configuration/
Communication/Ethernet configuration/FRONT:1.
84
2
1
Do not connect the IED front port to a LAN. Connect only a single local PC with
PCM600 to the front port. It is only intended for temporary use, such as
commissioning and testing.
1MRK 511 358-UEN A