Bay Control (Qcbay) - ABB Relion REC670 Applications Manual

Bay control version 2.1 iec
Hide thumbs Also See for Relion REC670:
Table of Contents

Advertisement

1MRK 511 358-UEN A
2 = Remote
3 = Faulty
4 = Not in use
5 = All
6 = Station
7 = Remote
PSTO = All, then it is no priority between operator places. All operator places are allowed to
operate.
According to IEC61850 standard the
29
Table 29: orCat attribute according to IEC61850
Value
0
1
2
3
4
5
6
7
8
13.3.1.1

Bay control (QCBAY)

The Bay control (QCBAY) is used to handle the selection of the operator place per bay. The
function gives permission to operate from two main types of locations either from Remote
(for example, control centre or station HMI) or from Local (local HMI on the IED) or from all
(Local and Remote). The Local/Remote switch position can also be set to Off, which means no
operator place selected that is, operation is not possible either from local or from remote.
For IEC 61850-8-1 communication, the Bay Control function can be set to discriminate between
commands with orCat station and remote (2 and 3). The selection is then done through the
IEC61850-8-1 edition 2 command LocSta.
QCBAY also provides blocking functions that can be distributed to different apparatuses
within the bay. There are two different blocking alternatives:
Blocking of update of positions
Blocking of commands
Application manual
2,3,4,5,6
4,5,6
4,5,6
1,2,3,4,5,6
2,4,5,6
3,4,5,6
Description
not-supported
bay-control
station-control
remote-control
automatic-bay
automatic-station
automatic-remote
maintenance
process
orCat attribute in originator category are defined in
Section 13
Control
Table
M16595-3 v7
259