Boolean 16 To Integer Conversion B16I; Identification; Application - ABB Relion REC670 Applications Manual

Bay control version 2.1 iec
Hide thumbs Also See for Relion REC670:
Table of Contents

Advertisement

Section 15
Logic
15.8

Boolean 16 to Integer conversion B16I

15.8.1

Identification

Function description
Boolean 16 to integer conversion
15.8.2

Application

Boolean 16 to integer conversion function B16I is used to transform a set of 16 binary (logical)
signals into an integer. It can be used – for example, to connect logical output signals from a
function (like distance protection) to integer inputs from another function (like line differential
protection). B16I does not have a logical node mapping.
The Boolean 16 to integer conversion function (B16I) will transfer a combination of up to 16
binary inputs INx where 1≤x≤16 to an integer. Each INx represents a value according to the
table below from 0 to 32768. This follows the general formula: INx = 2
of all the values on the activated INx will be available on the output OUT as a sum of the values
of all the inputs INx that are activated. OUT is an integer. When all INx where 1≤x≤16 are
activated that is = Boolean 1 it corresponds to that integer 65535 is available on the output
OUT. B16I function is designed for receiving up to 16 booleans input locally. If the BLOCK input
is activated, it will freeze the output at the last value.
Values of each of the different OUTx from function block B16I for 1≤x≤16.
The sum of the value on each INx corresponds to the integer presented on the output OUT on
the function block B16I.
Name of input
IN1
IN2
IN3
IN4
IN5
IN6
IN7
IN8
IN9
IN10
IN11
IN12
IN13
IN14
IN15
IN16
366
IEC 61850
identification
B16I
Type
Default
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
IEC 60617
ANSI/IEEE C37.2
identification
device number
-
-
x-1
Description
Value when
activated
Input 1
1
Input 2
2
Input 3
4
Input 4
8
Input 5
16
Input 6
32
Input 7
64
Input 8
128
Input 9
256
Input 10
512
Input 11
1024
Input 12
2048
Input 13
4096
Input 14
8192
Input 15
16384
Input 16
32768
1MRK 511 358-UEN A
SEMOD175715-1 v1
SEMOD175721-2 v2
SEMOD175832-4 v4
where 1≤x≤16. The sum
Value when
deactivated
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Application manual