1MRK 511 358-UEN A
Set value for parameter
"CurrentInput"
phase3 - phase1
12
13
MaxPh-Ph
14
MinPh-Ph
15
UnbalancePh-Ph
The user can select, by a setting parameter
voltage quantities shown in table 24.
Table 24: Available selection for voltage quantity within CVGAPC function
Set value for parameter
"VoltageInput"
phase1
1
2
phase2
phase3
3
PosSeq
4
-NegSeq
5
-3*ZeroSeq
6
MaxPh
7
MinPh
8
UnbalancePh
9
phase1 - phase2
10
phase2 - phase3
11
12
phase3 - phase1
Table continues on next page
Application manual
Comment
CVGAPC function will measure the current phasor internally calculated as
the vector difference between the phase L3 current phasor and phase L1
current phasor ( IL3-IL1)
CVGAPC function will measure ph-ph current phasor with the maximum
magnitude
CVGAPC function will measure ph-ph current phasor with the minimum
magnitude
CVGAPC function will measure magnitude of unbalance current, which is
internally calculated as the algebraic magnitude difference between the
ph-ph current phasor with maximum magnitude and ph-ph current
phasor with minimum magnitude. Phase angle will be set to 0° all the
time
VoltageInput , to measure one of the following
Comment
CVGAPC function will measure the phase L1 voltage phasor
CVGAPC function will measure the phase L2 voltage phasor
CVGAPC function will measure the phase L3 voltage phasor
CVGAPC function will measure internally calculated positive sequence
voltage phasor
CVGAPC function will measure internally calculated negative sequence
voltage phasor. This voltage phasor will be intentionally rotated for 180°
in order to enable easier settings for the directional feature when used.
CVGAPC function will measure internally calculated zero sequence voltage
phasor multiplied by factor 3. This voltage phasor will be intentionally
rotated for 180° in order to enable easier settings for the directional
feature when used.
CVGAPC function will measure voltage phasor of the phase with
maximum magnitude
CVGAPC function will measure voltage phasor of the phase with
minimum magnitude
CVGAPC function will measure magnitude of unbalance voltage, which is
internally calculated as the algebraic magnitude difference between the
voltage phasor of the phase with maximum magnitude and voltage
phasor of the phase with minimum magnitude. Phase angle will be set to
0° all the time
CVGAPC function will measure the voltage phasor internally calculated as
the vector difference between the phase L1 voltage phasor and phase L2
voltage phasor (UL1-UL2)
CVGAPC function will measure the voltage phasor internally calculated as
the vector difference between the phase L2 voltage phasor and phase L3
voltage phasor (UL2-UL3)
CVGAPC function will measure the voltage phasor internally calculated as
the vector difference between the phase L3 voltage phasor and phase L1
voltage phasor (UL3-UL1)